Mounting:
The STREAMTEK™ Cabinet Panel Cooler must be vertically mounted, on a flat surface surface for all enclosure types. The STREAMTEK™ Cabinet Panel Cooler system is easy to install through a 1-1/8" diameter drilled hole or electrical knockout.
Humidity:
It's important to close off any openings and any vents that may bring in ambient air, especially in warm or hot high humidity environments. The relative humidity inside the enclosure stabilizes at 45% for all continuous operating Cabinet Panel Coolers.
Filtration:
All STREAMTEK™ Cabinet Panel Cooler systems include an auto drain 5 micron dirt and water filter. This filter is imperative to prevent any accidental water flow into the enclosure. If oil is present in the compressed air supply, use an oil filter within at least .3 micron rating.
Environmental Considerations
NEMA 12 (IP52) - Cabinet Panel Coolers (oil-tight, dust-tight) are used in industrial environemnts where no liquids can come in contact with the unit. Constructed of Stainless Steel (Type 303) to withstand harsh corrosive environments.
NEMA 4/4X (IP56) - Designed for Electronic Control Panels - Splash resistant, oil-tight, and dust-tight for use in wash down environments as well as outdoor use. When the Panel Cooler is not operating a low pressure relief valve closes and seals to maintain the integrity of your NEMA 4 cabinet enclosure. Constructed of Stainless Steel (Type 303) for long life in wet environments. |
NEMA 12 (IP52) - Dust, Oil, and Corrosion Resistant |
Model No. |
Capacity Btu/hr. |
Capacity Kcal/hr. |
Air Consumption
SCFM @ 80 PSI |
Air Consumption
SLPM @ 5.5 Bar |
Sound Level |
STCC1208 |
550 |
139 |
8 |
226 |
67* |
STCC1215 |
1,100 |
277 |
15 |
425 |
73* |
STCC1225 |
1,800 |
454 |
25 |
708 |
74* |
STCC1230 |
2,060 |
519 |
30 |
849 |
74* |
STCC1240 |
2,800 |
706 |
40 |
1,132 |
80* |
STCC1250 |
3,400 |
857 |
(2 x CC1215) |
850 |
|
STCC1260 |
4,000 |
1008 |
(2 x CC1230) |
1,698 |
|
STCC1270 |
4,800 |
1210 |
(CC1230 & CC1240) |
1,981 |
|
STCC1280 |
5,600 |
1411 |
(2 x CC1240) |
2,264 |
|
|
NEMA 4/4X (IP56) - Dust, Oil, Corrosion, and Splash Resistant |
Model No. |
Capacity Btu/hr. |
Capacity Kcal/hr. |
Air Consumption
SCFM @ 80 PSI |
Air Consumption
SLPM @ 5.5 Bar |
Sound Level |
STCC408 |
550 |
139 |
8 |
226 |
67* |
STCC415 |
1,100 |
277 |
15 |
425 |
73* |
STCC425 |
1,800 |
454 |
25 |
708 |
74* |
STCC430 |
2,060 |
519 |
30 |
849 |
74* |
STCC440 |
2,800 |
706 |
40 |
1,132 |
80* |
*With Optional Cold Muffler installed |
|