Specifications

Mounting:
The STREAMTEK™ Cabinet Panel Cooler must be vertically mounted, on a flat surface surface for all enclosure types. The STREAMTEK™ Cabinet Panel Cooler system is easy to install through a 1-1/8" diameter drilled hole or electrical knockout.

Humidity:
It's important to close off any openings and any vents that may bring in ambient air, especially in warm or hot high humidity environments. The relative humidity inside the enclosure stabilizes at 45% for all continuous operating Cabinet Panel Coolers.

Filtration:
All STREAMTEK™ Cabinet Panel Cooler systems include an auto drain 5 micron dirt and water filter. This filter is imperative to prevent any accidental water flow into the enclosure. If oil is present in the compressed air supply, use an oil filter within at least .3 micron rating.

Environmental Considerations
NEMA 12 (IP52) - Cabinet Panel Coolers (oil-tight, dust-tight) are used in industrial environemnts where no liquids can come in contact with the unit. Constructed of Stainless Steel (Type 303) to withstand harsh corrosive environments.

NEMA 4/4X (IP56) - Designed for Electronic Control Panels - Splash resistant, oil-tight, and dust-tight for use in wash down environments as well as outdoor use. When the Panel Cooler is not operating a low pressure relief valve closes and seals to maintain the integrity of your NEMA 4 cabinet enclosure. Constructed of Stainless Steel (Type 303) for long life in wet environments.

NEMA 12 (IP52) - Dust, Oil, and Corrosion Resistant
Model No. Capacity Btu/hr. Capacity Kcal/hr. Air Consumption
SCFM @ 80 PSI
Air Consumption
SLPM @ 5.5 Bar
Sound Level
STCC1208 550 139 8 226 67*
STCC1215 1,100 277 15 425 73*
STCC1225 1,800 454 25 708 74*
STCC1230 2,060 519 30 849 74*
STCC1240 2,800 706 40 1,132 80*
STCC1250 3,400 857 (2 x CC1215) 850  
STCC1260 4,000 1008 (2 x CC1230) 1,698  
STCC1270 4,800 1210 (CC1230 & CC1240) 1,981  
STCC1280 5,600 1411 (2 x CC1240) 2,264  

NEMA 4/4X (IP56) - Dust, Oil, Corrosion, and Splash Resistant
Model No. Capacity Btu/hr. Capacity Kcal/hr. Air Consumption
SCFM @ 80 PSI
Air Consumption
SLPM @ 5.5 Bar
Sound Level
STCC408 550 139 8 226 67*
STCC415 1,100 277 15 425 73*
STCC425 1,800 454 25 708 74*
STCC430 2,060 519 30 849 74*
STCC440 2,800 706 40 1,132 80*
*With Optional Cold Muffler installed
 
 
 
Important Notice: By purchasing products from this Site, you acknowledge and agree that you have read and accept the Terms and Conditions of this online store. For more information email us at: info@iprocessmart.com
 
Copyright © 2010 iProcesSmart™.com
 
 
 
iProcesSmart Home Page of Industrial Process Equipment 

Temperature
Level
Pressure
Flow
Environmental
Instruments
Filtration
Valves
Electrical
Logic
Motion
Controls
TechSmart
Manufacturers
Company Info
Terms of Service
Site Security
Your Privacy
Support
Customers
Suppliers
News

 

 

SEARCH  INVENTORY



 

 

SEARCH  CATALOG


Boolean: 

Case