Positive, negative and
differential pressures can be measured within a full span accuracy
of ± 0.5 with the Dwyer Series 616W Differential Pressure
Transmitter. Units are enclosed in a polycarbonate case, rated NEMA 4X
(IP66) and operate by sensing the pressure of air and compatible gases
then sending a standard 4-20mA output signal. Versatile circuit design
enables operation in 2,3,4 wire current loops, and a wide range of
models are available factory calibrated to specific ranges. The span
and zero controls are for use when checking calibration. They are not
intended for re-ranging to a significantly different span. The LCD (as
shown above) allows local indication of pressure, if LCD is not
needed, drop from model number.
|
PHYSICAL
DATA GENERAL Pressure Connection: Barbed, dual size to fit 1/8" and 3/16" (3.2 and 4.8 mm) I.D. rubber or vinyl tubing. Media compatiblity: Air and compatible, non-corrosive, non-combustible gases. Housing: Gray Polycarbonate, NEMA 4X enclosure. Adjustments: Potentiometers for zero and span. Weight: 9 ounces (255 grams), 10 ounces (283 grams) - LCD. ELECTRICAL Power Supply: 10-35 VDC (2. 3. or 4 wire), 16-26 VAC (4 wire). Output Signal: 4-20 mA DC (limited at 38 mA DC). Loop Resistance: DC; 0-1300 Ohms maximum, AC; 0-1200 Ohms maximum Current Consumption: DC; 38 mA maximum. AC; 76 mA maximum. Electrical Connections: Screw Type terminal block. PERFORMANCE AT 70°F (21.1°C) Accuracy: ± 0.5% F.S. Stability: ± 1% FS/year. Zero Output: 4 mA DC. Span Output: 16 mA DC. Warm-up time: 10 minutes. ENVIRONMENTAL Operating Temperature: 20 to 120°F (-6.7 to 49°C). Thermal Errors: ± 0.02%/°F typical.
|